Section 13.1
Sizing example: one-bath electric ADU in Wisconsin
A one-bedroom backyard ADU in Wisconsin, all electric, needs 3.0 GPM at a 68 F rise. Rinnai's map puts Wisconsin ground water at 37 to 42 F[1], and this example uses 37 F. Only the two 36 kW models deliver that flow.
- Fixtures at the same time
- WaterSense 2.0 GPM shower plus a 1.0 GPM bathroom sink, 3.0 GPM in total
- Rise
- 105 F minus 37 F = 68 F
- Heat needed
- 500.4 x 3.0 x 68 = about 102,000 BTU/h, or about 30 kW
| Model | Flow at 68 F rise | Against 3.0 GPM | Manufacturer requirement |
|---|---|---|---|
| Stiebel Eltron Tempra 36 Trend / Plus | 3.7 GPM | Delivers 3.0 GPM | 3 x 50 A draw, breakers 3 x 50 A, 300 A main service |
| EcoSmart ECO 36 | 3.6 GPM | Delivers 3.0 GPM | 150 A draw, breakers 4 x 40 A DP, 300 A main service |
| EcoSmart ECO 8 | 0.8 GPM | Short by 2.2 GPM | 33 A draw, breakers 1 x 40 A DP |
| Stiebel Eltron Tempra 12 Trend / Plus | 1.2 GPM | Short by 1.8 GPM | 50 A draw, breakers 1 x 50 A, 100 A main service |
| EcoSmart ECO 11 | 1.3 GPM | Short by 1.7 GPM | 54 A draw, breakers 1 x 60 A DP |
| Stiebel Eltron Tempra 15 Trend / Plus | 1.5 GPM | Short by 1.5 GPM | 2 x 30 A draw, breakers 2 x 30 A, 100 A main service |
| EcoSmart ECO 18 | 1.8 GPM | Short by 1.2 GPM | 75 A draw, breakers 2 x 40 A DP, 150 A main service |
| Stiebel Eltron Tempra 20 Trend / Plus | 2.0 GPM | Short by 1.0 GPM | 2 x 40 A draw, breakers 2 x 40 A, 125 A main service |
| Stiebel Eltron Tempra 24 Trend / Plus | 2.5 GPM | Short by 0.5 GPM | 2 x 50 A draw, breakers 2 x 50 A, 150 A main service |
| EcoSmart ECO 24 | 2.4 GPM | Short by 0.6 GPM | 100 A draw, breakers 3 x 40 A DP, 200 A main service |
| EcoSmart ECO 27 | 2.7 GPM | Short by 0.3 GPM | 113 A draw, breakers 3 x 40 A DP, 200 A main service |
| Stiebel Eltron Tempra 29 Trend / Plus | 2.9 GPM | Short by 0.1 GPM | 3 x 40 A draw, breakers 3 x 40 A, 200 A main service |
13.1.1 Result
No unit under 36 kW delivers 3.0 GPM at a 68 F rise. A 36 kW unit draws 150 A on either manufacturer's sheet[2][3], more than many ADU subpanels carry. A 1.5 GPM showerhead with a 0.5 GPM sink aerator lowers the required flow to 2.0 GPM. The 24 kW models deliver that. The Tempra table lists 2.52 GPM at a 66 F rise for the Tempra 24[2]. A separate point-of-use unit at the sink is the other option.
Whether the main service and the ADU feeder can carry any of these loads is for a licensed electrician to determine.
Notes and sources
- Rinnai, non-condensing tankless brochure with United States Ground Water Temperature Map and V53De table, 06/2022 (PDF hosted by Woodstove Pro)
- Stiebel Eltron, Tempra table of flow rates at temperature rises (technical bulletin PDF)
- EcoSmart, electric tankless sizing sheet with zone table, 105 F set point (PDF)